VULNERABILITY INTELLIGENCE
CVE-2023-5768
CVSS score5.9 MEDIUM
EPSS probability0.41%
CISA KEVNot currently listed
Published2023-12-04
Last modified2026-06-17
CVSS vectorCVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H
Description
A vulnerability exists in the HCI IEC 60870-5-104 that affects the RTU500 series product versions listed below. Incomplete or wrong received APDU frame layout may cause blocking on link layer. Error reason was an endless blocking when reading incoming frames on link layer with wrong length information of APDU or delayed reception of data octets. Only communication link of affected HCI IEC 60870-5-104 is blocked. If attack sequence stops the communication to the previously attacked link gets normal again.
Weakness classification
- nvd@nist.gov: CWE-79
Primary references
- cybersecurity@hitachienergy.com — Vendor Advisory
- af854a3a-2127-422b-91ae-364da2661108 — Vendor Advisory