VULNERABILITY INTELLIGENCE

CVE-2022-33174

CVSS score9.8 CRITICAL
EPSS probability14.12%
CISA KEVNot currently listed
Published2022-06-13
Last modified2026-06-17
CVSS vectorCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

Description

Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 allows remote authorization bypass in the web interface. To exploit the vulnerability, an attacker must send an HTTP packet to the data retrieval interface (/cgi/get_param.cgi) with the tmpToken cookie set to an empty string followed by a semicolon. This bypasses an active session authorization check. This can be then used to fetch the values of protected sys.passwd and sys.su.name fields that contain the username and password in cleartext.

Weakness classification

  • nvd@nist.gov: CWE-863

Primary references