VULNERABILITY INTELLIGENCE
CVE-2018-13814
Description
A vulnerability has been identified in SIMATIC HMI Comfort Panels 4" - 22" (All versions < V14), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (All versions < V14), SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 and KTP900F (All versions < V14), SIMATIC WinCC Runtime Advanced (All versions < V14), SIMATIC WinCC Runtime Professional (All versions < V14), SIMATIC WinCC (TIA Portal) (All versions < V14), SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel) (All versions). The integrated web server (port 80/tcp and port 443/tcp) of the affected devices could allow an attacker to inject HTTP headers. An attacker must trick a valid user who is authenticated to the device into clicking on a malicious link to exploit the vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
Weakness classification
- CWE-20: Improper Input Validation
- CWE-113: Improper Neutralization of CRLF Sequences in HTTP Headers ('HTTP Request/Response Splitting')
Primary references
- productcert@siemens.com — Third Party Advisory, VDB Entry
- productcert@siemens.com — Vendor Advisory
- af854a3a-2127-422b-91ae-364da2661108 — Third Party Advisory, VDB Entry
- af854a3a-2127-422b-91ae-364da2661108 — Vendor Advisory